The charts below allow you to easily select the right American APT Series tank for standard-size pumps between 2-1/2 and 30 gallons in capacity and for 20-40 PSI, 30-50 PSI and 40-60 PSI pressure ranges. Minimum run times shown (from start-up) are 1 minute, 1-1/2 minutes and 2 minutes. For example, for a system that delivers 12 GPM at 30-50 PSI, with a minimum run time of 1 minute, Chart 1 indicates that the proper tank is the APT-45.
|
If proper tank selection cannot be made using Chart 1, follow this procedure. First, find the “drawdown multiplier” by matching the pump start-up and shut-off pressures on Chart 2. For example, the multiplier for a 30-50 PSI pressure range is .31.
Next, insert the pump GPM capacity and desired minimum run time into this formula: To assume dependable drawdown volumes, and in keeping with present industry practice, drawdowns are based on Boyle’s Law. For example, using a 10 GPM pump, a one-minute minimum run time, and a 30-50 PSI pressure range, the formula is as follows: Then, using Chart 3, select the tank that has a minimum volume that meets or exceeds your minimum volume requirement and supplies adequate drawdown at the required pressure range. Minimum drawdown equals Pump GPM X Minimum Run Time. Therefore, in the above example, select the APT-45 45-gallon tank. It provides adequate drawdown at 30-50 PSI.
|